The Eaton Moeller® series DILMP 4-pole contactor is a high-performance electrical switching device designed for a variety of industrial and commercial applications. It is characterized by its compact size, robust construction, and reliable operation.
Key features and specifications:
- Product name: Eaton Moeller® series DILMP 4-pole contactor
- Part number: DILMP160(RAC240)
- EAN: 4015081094813
- Dimensions:
- Length/Depth: 160 mm
- Height: 170 mm
- Width: 122 mm
- Weight: 2.73 kg
- Certifications:
- UL 60947-4-1 (UL File No.: E29096)
- CSA-C22.2 No. 60947-4-1-14 (CSA File No.: 012528, CSA Class No.: 2411-03, 3211-04)
- UL
- VDE 0660
- UL Category Control No.: NLDX
- CE
- IEC/EN 60947-4-1
- CSA
- IEC/EN 60947
- Tradename: DILMP
- Product type: 4-pole contactor
- Product subtype: None
- Catalog notes: Contacts according to EN 50012
Additional information:
- The DILMP contactor is designed for use in AC-3 and AC-4 applications.
- It features a compact and modular design, making it easy to install and maintain.
- The contactor is equipped with a variety of auxiliary contacts, which can be used for monitoring and control purposes.
- It is also available with a variety of coil voltages and operating frequencies.
Applications:
The DILMP contactor is suitable for a wide range of applications, including:
- Motor control
- Lighting control
- Heating and ventilation
- Pump control
- Machine tools
- Industrial automation
Overall, the Eaton Moeller® series DILMP 4-pole contactor is a reliable and versatile component that can be used in a variety of electrical control systems.
General specifications
Product name: Eaton Moeller® series DILMP 4-pole contactor
Part no.: DILMP160(RAC240)
EAN: 4015081094813
Product Length/Depth: 160 millimetre
Product height: 170 millimetre
Product width: 122 millimetre
Product weight: 2.73 kilogram
Certifications:
UL 60947-4-1
UL File No.: E29096
CSA-C22.2 No. 60947-4-1-14
CSA File No.: 012528
CSA Class No.: 2411-03, 3211-04
UL; VDE 0660; UL Category Control No.: NLDX
CE; IEC/EN 60947-4-1
CSA; ZEC/EN 60947
UL File No.: E29096
CSA-C22.2 No. 60947-4-1-14
CSA File No.: 012528
CSA Class No.: 2411-03, 3211-04
UL; VDE 0660; UL Category Control No.: NLDX
CE; IEC/EN 60947-4-1
CSA; ZEC/EN 60947
Product Tradename: DILMP
Product Type: 4-pole contactor
Product Sub Type: None
Catalog Notes: Contacts according to EN 50012
Features & Functions
Fitted with: Suppressor circuit in actuating electronics
General information
Application: Contactors for 4 pole electric consumers
Connection: Screw terminals
Degree of protection: IP00
Lifespan, mechanical:
10,000,000 Operations (AC operated)
10,000,000 Operations (DC operated)
10,000,000 Operations (DC operated)
Operating frequency:
3600 mechanical Operations/h (AC operated)
3600 mechanical Operations/h (DC operated)
3600 mechanical Operations/h (DC operated)
Overvoltage category: III
Pollution degree: 3
Product category: Contactors
Protection: Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp): 8000 V AC
Residual current: 1 mA (with actuation of A1 – A2 by the electronics with “0” signal)
Resistance per pole: 0.6 mΩ
Utilization category:
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage type: AC
Ambient conditions, mechanical
Shock resistance:
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Altitude: Max. 2000 m
Ambient operating temperature – min: -25 °C
Ambient operating temperature – max: 60 °C
Ambient operating temperature (enclosed) – min: -25 °C
Ambient operating temperature (enclosed) – max: 40 °C
Ambient storage temperature – min: -40 °C
Ambient storage temperature – max: 80 °C
Climatic proofing: Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-3
Damp heat, constant, to IEC 60068-2-3
Electro magnetic compatibility
Interference immunity
According to EN 60947-1
Terminal capacities
Terminal capacity (copper band)
2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (flexible with ferrule)
2 x (0.75 – 1.5) mm²
1 x (0.75 – 1.5) mm²
1 x (0.75 – 1.5) mm²
Terminal capacity (flexible)
2 x (0.75 – 2.5) mm²
1 x (0.75 – 2.5) mm²
1 x (0.75 – 2.5) mm²
Terminal capacity (solid)
1 x (0.75 – 2.5) mm²
1 x (0.75 – 4) mm², Control circuit cables
2 x (0.75 – 4) mm², Control circuit cables
1 x (0.75 – 4) mm², Control circuit cables
2 x (0.75 – 4) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)
18 – 14, Control circuit cables
8 – 3/0, Main cables
8 – 3/0, Main cables
Terminal capacity (stranded)
1 x (16 – 120) mm², Main cables
2 x (16 – 95) mm², Main cables
2 x (16 – 95) mm², Main cables
Stripping length (main cable)
15 mm
Stripping length (control circuit cable)
10 mm
Screw size
M3.5, Terminal screw, Control circuit cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
M10, Terminal screw, Main cables
5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
M10, Terminal screw, Main cables
Screwdriver size
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Tightening torque
14 Nm, Screw terminals, Main cables
1.2 Nm, Screw terminals, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Electrical rating
Rated breaking capacity at 220/230 V: 950 A
Rated breaking capacity at 380/400 V: 950 A
Rated breaking capacity at 500 V: 950 A
Rated breaking capacity at 660/690 V: 750 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V: 160 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V: 95 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V: 95 A
Rated operational current (Ie) at AC-3, 440 V: 95 A
Rated operational current (Ie) at AC-3, 500 V: 95 A
Rated operational current (Ie) at AC-3, 660 V, 690 V: 80 A
Rated operational current (Ie) at DC-1, 60 V: 160 A
Rated operational current (Ie) at DC-1, 110 V: 160 A
Rated operational current (Ie) at DC-1, 220 V: 160 A
Rated insulation voltage (Ui): 690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947): 1330 A
Rated operational power at AC-1, 220/230 V, 50 Hz: 58 kW
Rated operational power at AC-1, 240 V, 50 Hz: 63 kW
Rated operational power at AC-1, 380/400 V, 50 Hz: 100 kW
Rated operational power at AC-1, 415 V, 50 Hz: 109 kW
Rated operational power at AC-1, 440 V, 50 Hz: 116 kW
Rated operational power at AC-1, 500 V, 50 Hz: 132 kW
Rated operational power at AC-1, 690 V, 50 Hz: 174 kW
Rated operational power at AC-3, 240 V, 50 Hz: 33 kW
Rated operational power at AC-3, 380/400 V, 50 Hz: 45 kW
Rated operational power at AC-3, 415 V, 50 Hz: 57 kW
Rated operational power at AC-3, 440 V, 50 Hz: 60 kW
Rated operational power at AC-3, 500 V, 50 Hz: 70 kW
Rated operational power at AC-3, 690 V, 50 Hz: 75 kW
Rated operational voltage (Ue) at AC – max: 690 V
Short-circuit rating
Short-circuit current rating (basic rating)
10 kA, SCCR (UL/CSA)
600 A, max. Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
600 A, max. Fuse, SCCR (UL/CSA)
600 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)
250 A, max. CB, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)
350 A, max. CB, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
30/100 kA, Fuse, SCCR (UL/CSA)
300/300 A, Class J, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V: 250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V: 200 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V: 160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V: 160 A gG/gL
Conventional thermal current Ith
Conventional thermal current ith (1-pole, enclosed) 373 A
Conventional thermal current ith (3-pole, enclosed) 128 A
Conventional thermal current ith at 55°C (3-pole, open) 143 A
Conventional thermal current ith at 60°C (3-pole, open) 138 A
Conventional thermal current ith of main contacts (1-pole, open) 415 A
Switching capacity
Switching capacity (main contacts, general use)
125 A, Maximum motor rating (UL/CSA)
Magnet system
Drop-out voltage
AC operated: 0.6 – 0.25 x UC, AC operated
Duty factor: 100 %
Pick-up voltage
0.8 – 1.15 V AC/DC x Us
0.8 – 1.15 V AC x Uc
0.8 – 1.15 V AC x Uc
Power consumption, pick-up, 50 Hz
180 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz
180 VA, Dual-frequency coil in a cold state and 1.0 x Us
150 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
150 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz
2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz
2.3 W, Dual-frequency coil in a cold state and 1.0 x Us
3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz – min: 190 V
Rated control supply voltage (Us) at AC, 50 Hz – max: 240 V
Rated control supply voltage (Us) at AC, 60 Hz – min: 190 V
Rated control supply voltage (Us) at AC, 60 Hz – max: 240 V
Rated control supply voltage (Us) at DC – min: 0 V
Rated control supply voltage (Us) at DC – max>: 0 V
Switching time (AC operated, make contacts, closing delay) – min: 28 ms
Switching time (AC operated, make contacts, closing delay) – max: 33 ms
Switching time (AC operated, make contacts, opening delay) – min: 35 ms
Switching time (AC operated, make contacts, opening delay) – max: 41 ms
Motor rating
Assigned motor power at 115/120 V, 60 Hz, 1-phase: 7.5 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase: 25 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase: 15 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase: 40 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase: 75 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase: 100 HP
Communication
Connection to SmartWire-DT: No
Contacts
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of contacts (normally closed) as main contact: 0
Safety
Safe isolation
440 V AC, Between coil and contacts, According to EN 61140
440 V AC, Between the contacts, According to EN 61140
440 V AC, Between the contacts, According to EN 61140
Special purpose ratings
Special purpose rating of ballast electrical discharge lamps
100 A (600V 60Hz 3phase, 347V 60Hz 1phase)
100 A (480V 60Hz 3phase, 277V 60Hz 1phase)
100 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Special purpose rating of elevator control
77 A, 600 V 60 Hz 3-ph, (UL/CSA)
75 HP, 600 V 60 Hz 3-ph, (UL/CSA)
80 A, 240 V 60 Hz 3-ph, (UL/CSA)
30 HP, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 200 V 60 Hz 3-ph, (UL/CSA)
60 HP, 480 V 60 Hz 3-ph, (UL/CSA)
62.1 A, 200 V 60 Hz 3-ph, (UL/CSA)
77 A, 480 V 60 Hz 3-ph, (UL/CSA)
75 HP, 600 V 60 Hz 3-ph, (UL/CSA)
80 A, 240 V 60 Hz 3-ph, (UL/CSA)
30 HP, 240 V 60 Hz 3-ph, (UL/CSA)
20 HP, 200 V 60 Hz 3-ph, (UL/CSA)
60 HP, 480 V 60 Hz 3-ph, (UL/CSA)
62.1 A, 200 V 60 Hz 3-ph, (UL/CSA)
77 A, 480 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)
90 A, FLA 480 V 60 Hz 3phase; (CSA)
70 A, FLA 600 V 60 Hz 3phase; (CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
420 A, LRA 600 V 60 Hz 3phase; (CSA)
70 A, FLA 600 V 60 Hz 3phase; (CSA)
540 A, LRA 480 V 60 Hz 3phase; (CSA)
420 A, LRA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating
100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
110 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
110 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps
100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Design verification
Equipment heat dissipation, current-dependent Pvid: 36.3 W
Heat dissipation capacity Pdiss: 0 W
Heat dissipation per pole, current-dependent Pvid: 12.1 W
Rated operational current for specified heat dissipation (In): 160 A
Static heat dissipation, non-current-dependent Pvs: 2.3 W
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 9.0
Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss13-27-37-10-03 [AAB718020])
Rated control supply voltage AC 50 Hz: 190 – 240 V
Rated control supply voltage AC 60 Hz: 190 – 240 V
Rated control supply voltage DC: 0 – 0 V
Voltage type for actuating: AC
Number of normally closed contacts as main contact: 0
Number of normally open contacts as main contact: 4
Type of electrical connection of main circuit: Screw connection
Operating voltage AC 50 Hz: 230 – 690 V
Operating voltage AC 60 Hz: 230 – 690 V
Rated operation current Ie at AC-1, 400 V: 160 A
Rated operation current Ie at AC-3, 400 V: 95 A
Rated operation power at AC-3, 400 V: 45 kW
Rated operation current Ie at AC-4, 400 V: 65 A
Rated operation power at AC-4, 400 V: 33 kW
Rated operation power NEMA: 55 kW
Number of auxiliary contacts as normally open contact: 0
Number of auxiliary contacts as normally closed contact: 0
Modular version: No
Width: 122 mm
Height: 170 mm
Depth: 160 mm
Weight | 2,8 kg |
---|---|
Dimensions | 14 × 18 × 17 cm |
Manufacturer | EATON |
Reviews
There are no reviews yet.